PVC Pressure Pipe and
fittings are combustible materials, however, they may be installed in
noncombustible buildings. In all cases the model building codes have determined
that PVC must be protected at penetrations of walls, floors, ceilings and fire
resistance rated assemblies. The method of protecting the pipe penetration is
by a through penetration protection assembly that has been tested and rated in
accordance with ASTM E814. This assembly must have been tested and given an "F"
rating. The "F" rating must be a minimum of the hourly rating of the fire
resistance rated assembly that the PVC plastic pipe penetrates. Verify local
code interpretations related to through penetrations with the jurisdiction
having authority.